Detonation Flame Arrester MODEL 7661
We reply Monday to Friday, 9:00 a.m. to 6:00 p.m. (Mexico City time) · +52 55 2458 7374
Description
The Groth Model 7661 deflagration and detonation flame arrester inhibits flame propagation in gas piping systems. Its design makes it ideal for protecting liquid storage tanks containing NEC Group D gases (IEC Class IIA) with a Maximum Experimental Safe Gap (MESG) equal to or greater than 0.90 mm.
Compact with high flow capacity and low pressure drop
Elements can be easily removed in-line for cleaning and maintenance
Vertical or horizontal installation
For in-line or end-of-line deflagrations
Bidirectional with respect to flow and ignition source
Low pressure drop with multiple element sizes available for each flange size
Sizes: 4”x 16” to 12”x 30”
Housing materials: Carbon steel, stainless steel, Alloy C276
Element materials: Stainless steel, Alloy C276, or other corrosion-resistant alloys
Unstable detonations
Pre-ignition system pressure: up to 15.7 psia (1.08 bara)
Pre-ignition system temperatures: -4 to 140°F (-20 to 60°C)
Burn time tBT: 20 minutes
Many sizes certified per ATEX and/or the U.S. Coast Guard; consult the factory for more information
Sensor ports
Large inspection and cleaning ports
Swing bolts for quick element removal
Factory-installed thermocouples for flame detection