P&V Control Devices
My Cart
Total $0.00
Detonation Flame Arrester – Group D Gases MODEL 7658A
Detonation Flame Arrester – Group D Gases MODEL 7658A
Detonation Flame Arrester – Group D Gases MODEL 7658A Detonation Flame Arrester – Group D Gases MODEL 7658A

Detonation Flame Arrester – Group D Gases MODEL 7658A

Price on request

Description

The Groth Model 7658A Deflagration and Detonation Flame Arrester inhibits flame propagation in gas piping systems. Its design makes it ideal for protecting liquid storage tanks containing NEC Group D gases (IEC Class IIA).

Vertical or horizontal installation

In-line or end-of-line deflagrations

Unstable detonations

Burn time tBT: 10 minutes

Bidirectional with respect to flow and ignition source

Elements can be easily removed in-line for cleaning and maintenance, and are inexpensive to replace if necessary

Low pressure drop, with multiple element sizes available for each flange size

A thermocouple for flame detection is required per ATEX and USCG codes

Size: From 2″ (DN50) x 5″ (DN125) to 6″ (DN150) x 12″ (DN300)

Material: Standard housing material: carbon steel or stainless steel.

• Standard flame element material: stainless steel.

Pressure: Pre-ignition system pressure up to 15.7 psia (1.08 bara).

Certification:

• Certified per the ATEX Directive in compliance with EN ISO 16852:2010, Certificate #: IBExU12ATE X2160 X.

• USCG certified per 33 CFR Part 154 App. A Type II, Certificate #: CSA LO 4000-5704.

• A thermocouple for flame detection is required per ATEX and USCG regulations.

Temperature: Pre-ignition system temperatures: -4 to 140 °F (-20 to 60 °C).

Factory-installed thermocouples for flame detection

Other materials available

Sensor ports

Large inspection and cleaning ports

Swing bolts for quick element removal

×
×